This is a
Clicking the inclusion button in the module
Z-Wave is the international wireless protocol for communication in the Smart Home. This device is suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message (two-way communication) and every mains powered node can act as a repeater for other nodes (meshed network) in case the receiver is not in direct wireless range of the transmitter.
This device and every other certified Z-Wave device can be used together with any other certified Z-Wave device regardless of brand and origin as long as both are suited for the same frequency range.
If a device supports secure communication it will communicate with other devices secure as long as this device provides the same or a higher level of security. Otherwise it will automatically turn into a lower level of security to maintain backward compatibility.
For more information about Z-Wave technology, devices, white papers etc. please refer to www.z-wave.info.
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory default state. Please make sure to reset the device into factory default. You can do this by performing an Exclusion operation as described below in the manual. Every Z-Wave controller is able to perform this operation however it is recommended to use the primary controller of the previous network to make sure the very device is excluded properly from this network.
This device also allows to be reset without any involvement of a Z-Wave controller. This procedure should only be used when the primary controller is inoperable.
The Heatit Z-Relay can be factory reset by pressing the inclusion button in the module for at least 10 seconds.
ATTENTION: only authorized technicians under consideration of the country-specific installation guidelines/norms may do works with mains power. Prior to the assembly of the product, the voltage network has to be switched off and ensured against re-switching.
On factory default the device does not belong to any Z-Wave network. The device needs to be added to an existing wireless network to communicate with the devices of this network. This process is called Inclusion.
Devices can also be removed from a network. This process is called Exclusion. Both processes are initiated by the primary controller of the Z-Wave network. This controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is then performed doing a special manual action right on the device.
Temperature inputs
Input 1 and 2 can be used as temperature inputs by connecting NTC sensors to the inputs. The type of NTC sensor can be configured by means of configuration parameters 3 and 4.A temperature offset can be configured for each of the inputs by means of configuration parameters 5 and 6.
Flood sensor input
Input 3 is a flood sensor input where it is possible to connect a simple flood sensor. The flood sensor can be left lying on the floor (on an electrically insulating surface), or attached to the floor or a wall. Designed for flood detection, it senses water and other electrically conductive liquids. The sensitivity of the sensor can be configured by means of configuration parameter 14.
It is possible for the flood input to directly control the Heatit Z-Relay output, either to turn the relay output ON or OFF when a flood is detected, or when no flood is detected, see configuration parameters 12 and 13.
Relay Output
The relay output is a high power "normally open" (NO) contact that can be used for several purposes. It is possible to control the relay from the Z-Wave network, or it can be controlled by the flood sensor input.
The Heatit Z-Relay monitors the current used by the load connected to the relay output. The energy that the load consumes is calculated by means of the measured current and the voltage entered in configuration parameter 15. Energy data is sent to the controller through the Z-Wave network. These data values that the controller is able to receive are: current (A), power (Watt), and the energy consumed over time (kWh).
Here are a few hints for network installation if things dont work as expected.
Z-Wave devices control other Z-Wave devices. The relationship between one device controlling another device is called association. In order to control a different device, the controlling device needs to maintain a list of devices that will receive controlling commands. These lists are called association groups and they are always related to certain events (e.g. button pressed, sensor triggers, ...). In case the event happens all devices stored in the respective association group will receive the same wireless command wireless command, typically a 'Basic Set' Command.
Group Number | Maximum Nodes | Description |
---|---|---|
1 | 5 | lifeline |
2 | 5 | Sensor Multilevel Report for input 1. |
3 | 5 | Sensor Multilevel Report for input 2. |
4 | 5 | Basic Report On / Off when the flood sensor detects a flood. |
5 | 5 | Basic Set On / Off when the flood sensor detects a flood |
6 | 5 | Notification Report when the flood sensor detects a flood. |
Z-Wave products are supposed to work out of the box after inclusion, however certain configuration can adapt the function better to user needs or unlock further enhanced features.
IMPORTANT: Controllers may only allow configuring signed values. In order to set values in the range 128 ... 255 the value sent in the application shall be the desired value minus 256. For example: To set a parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56. In case of a two byte value the same logic applies: Values greater than 32768 may needed to be given as negative values too.
Configuration of the status LED.
Size: 1 Byte, Default Value: 1
Setting | Description |
---|---|
0 | LED turned off. |
1 | LED turned on. |
2 | LED flashing at 1 second intervals (½ Hz). |
3 | LED flashing at ½ second interval (1 Hz). |
Configure the percentage of light in the status LED, when the LED is turned on.
Size: 1 Byte, Default Value: 50
Setting | Description |
---|---|
1 - 100 | Brightness level of the LED |
Configures the thermistor type connected to input 1.
Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Input disabled. |
1 | 10K NTC |
Configures the thermistor type connected to input 2.
Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
0 | Input disabled. |
1 | 10K NTC |
Configures a temperature offset that can be added to the measured temperature in order to get a more accurate measurement from the thermistor on input 1. Size: 1 Byte, Default Value: 0
Setting | Description |
---|
Configures a temperature offset that can be added to the measured temperature in order to get a more accurate measurement from the thermistor on input 2. Size: 1 Byte, Default Value: 0
Setting | Description |
---|---|
-40 - 40 | -4,0 – 4,0°C. |
Configures the time interval between when sensor reports are transmitted for input 1.
Size: 2 Byte, Default Value: 6
Setting | Description |
---|
Configures the time interval between when sensor reports are transmitted for input 2.
Size: 2 Byte, Default Value: 6
Setting | Description |
---|
Configures the time interval between when notification reports for flood input 3. Size: 2 Byte, Default Value: 6
Setting | Description |
---|---|
0 - 8640 | 0 – 86 400 seconds. |
Configures the time interval between when meter reports for reporting the energy (kWh) consumed by the load connected to the relay output.
Size: 2 Byte, Default Value: 2
Setting | Description |
---|---|
0 - 8640 | 0 – 86 400 seconds. |
Configures the time that the flood input (input 3) has to be steady before the state is accepted as a valid state.gures the time that the flood input (input 3) has to be steady before the state is accepted as a valid state.
Size: 1 Byte, Default Value: 6
Setting | Description |
---|---|
0 - 60 | 0 – 60 seconds. |
Configures internal states that will cause the relay to be turned on.
Size: 1 Byte, Default Value: 1
Setting | Description |
---|---|
0 | Relay is not turned on automatically. |
1 | The relay is turned on when a flood is detected. |
2 | The relay is turned on when no flood is detected. |
Configures internal states that will cause the relay to be turned off.
Size: 1 Byte, Default Value: 2
Setting | Description |
---|---|
0 | Relay is not turned off automatically. |
1 | The relay is turned off when a flood is detected. |
2 | The relay is turned off when no flood is detected. |
Configures the threshold for input 3 that will cause a flood to be detected.
Size: 2 Byte, Default Value: 2048
Setting | Description |
---|---|
0 - 4095 | Low value means a low detection threshold, high value will cause the input to be more sensitive. |
Configures the value used for power calculation, as only the current for the load on the relay output is measured.
Size: 1 Byte, Default Value: 220
Setting | Description |
---|---|
0 - 250 | Volt |
Configures a constant value that will be used in power metering when this value is different from 0. This value specifies the actual load in Watt used for power metering. Size: 2 Byte, Default Value: 0
Setting | Description |
---|---|
0 - 6000 | Watt |
Dimensions | 100 x 100 x 46 mm |
Weight | 223 gr |
Hardware Platform | ZM5101 |
EAN | 7071236014126 |
IP Class | IP 55 |
Voltage | 230 V |
Load | 25 A |
Device Type | Relay |
Generic Device Class | Binary Switch |
Firmware Version | 00.08 |
Z-Wave Version | 04.3d |
Z-Wave Product Id | 0x019b.0x0003.0x0208 |
Frequency | Europe - 868,4 Mhz |
Maximum transmission power | 5 mW |